Voltage Stability of Long Transmission Line Equipped with a Thyristor Controlled Series Capacitor
- 1 Division of Electrical Engineering, Faculty of Engineering at Si Racha, Kasetsart University, 199 M.6, Tungsukhla, Si Racha, Chonburi, 20230, Thailand
Abstract
Problem statement: Power-Voltage curve provides very important information for voltage stability analysis. The exact long transmission line model consists of the resistance and the reactance. The resistance causes in the active line loss. It is not easy task to achieve the power-voltage curve characteristics of power system with the exact long line model equipeed with a Thyristor Controlled Series Capacitor (TCSC). Approach: This study applies the concept of the Newton-Raphson method to iteratively solve the nonlinear power flow equations. The Power-Voltage (P-V) curve charateristic of the system without line loss and with line loss are plotted and compared on various cases. Results: It is found from the study that the resistance of the line obviously provides the negative effects on the voltage stability. The line loss causes in the decrement of the critical point. In addition, it is found that the leading power factor can increase the critical point of P-V curve. Conclusion: The exact long line model should be considered for voltage stability analysis of the system with the long transmission line.
DOI: https://doi.org/10.3844/ajassp.2012.1491.1495
Copyright: © 2012 Prechanon Kumkratug. This is an open access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.
- 3,302 Views
- 2,998 Downloads
- 1 Citations
Download
Keywords
- Thyristor Controlled Series Capacitor (TCSC)
- Power-Voltage (P-V)
- Critical Clearing Time (CCT)
- Flexible AC Transmission System (FACTS)