By-pass Devices as Effective Means of Protection from the Hydraulic Hammer

Khalid S. Al-Rababa1
  • 1 Department of Mechanical Engineering, Tafila Applied University College Al-balqa’ Applied University, P.O. Box 179, Ai-Eys-66110, Jordan

Abstract

Switching-off the parallel working pump units causes sudden discharge changes in parallel pipe lines, as a result of that hydraulic shocks takes place. The damping of these shocks can be achieved by the installation of the by-pass devices between the parallel lines of the piping system. The analytical calculations demonstrate that the reduction in hydraulic shocks reaches 40% and considerable part of the electric power (from 5 up to 21%) is economized by using the by-pass devices, the duration of pressure decline decreases by more than 1,5 times. Comparison of the calculations based on the developed algorithm with the results of practical studies at the pumping station (Syrdarya) has shown good convergence of analytical and experimental outcomes.